HAWKE CABLE GLANDS
501/453 Universal
dimensions & sizing
installation instructions size Os-F
installation instructions size G-J
Application Outdoor or Indoor use. For use with single wire armoured 'W', wire braided 'X' and steel tape armoured 'Z' elastomer and plastic insulated cables. For particular use with cables that exhibit 'cold flow' characteristics.
Features Provides armour clamping using one clamping arrangement for all armour/braid types. Provides a diaphragm seal on the cables inner sheath which will not damage cable that has 'cold flow' characteristics. Provides an outer deluge seal to prevent moisture ingress to the cable armour/braid. Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.
Materials & Finishes The 501/453/Universal cable gland is manufactured as standard in brass, stainless steel and aluminium. NPT entries are nickel plated as standard. Full nickel plating by electroplating or electroless plating is also available, as are other materials on request.
 | |
|
 |
ICG 653 Universal
dimensions & sizing
installation instructions size Os-F
installation instructions size G-J
Application Outdoor or Indoor use. For use with single wire armoured 'W', wire braided 'X' and steel tape armoured 'Z' elastomer and plastic insulated cables. For particular use with :- a) Cables that are not effectively filled, compact and/or circular, have tape bedding or have hygroscopic fillers. b) Cables that exhibit 'cold flow' characteristics. c) Enclosures containing an ignition source in gas group IIC areas or containing an ignition source in a Zone 1 area and exceeding 2 litres in volume.
Features Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable. Assembly of the cable gland compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure. The compound chamber may be seperated from the cured compound to ensure that the chamber has been effectively filled. If required, external voids can be repaired. Provides armour clamping, using one clamping arrangement for all armour/braid types. Provides an outer deluge seal to prevent moisture ingress to the cable armour/braid. Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath. Two part sealing compound and assembly instructions are supplied with the cable gland.
Materials & Finishes The ICG 653/Universal cable gland is manufactured as standard in brass, tainless steel and aluminium. NPT entries are nickel plated as standard. Full nickel plating by electroplating or electroless plating is also available, as are other materials on request.
|
|